GE WES5120 5120-1106工控控制卡件
您必须将位置更改为Control Builder M中HW树中计划的正确值。硬件单元上的配置通常通过DIP开关完成。但PA设备通常没有DIP开关。在这种情况下,您可以使用Web界面通过PROFIBUS设置地址,如第77页的SetAddress所述。通过DP-V1进行配置Control Builder M内PA设备的配置仅用于使设备通过循环DP-V0通信在PROFIBUS上运行。只能配置I/O通信。PA设备的内部行为只能通过DP-V1通信进行非循环配置。使用DP-V1配置,您可以更改设备的操作模式、定义故障安全行为、配置限值、定义滤波器和线性化以及调整校准参数。所有这些配置也可能影响循环通信。例如,如果改变了操作模式,则可在PROFIBUS上添加其他变量。
You have to change the position to the correct value that is planned in the HW tree in the Control Builder M. The configuration on the
hardware unit is typically done via DIP switches. But PA devices typically do not
have a DIP switch. In this case you can set the address via the PROFIBUS using the
Web interface as described in SetAddress on page 77.
Configuration via DP-V1
The configuration for PA-devices within the Control Builder M is only to get the
device running on PROFIBUS with the cyclic DP-V0 communication. Only the I/Ocommunication can be configured. The internal behavior of the PA-device can only
be configured acyclic via DP-V1 communication.With the DP-V1 configuration you can change the operating mode of the device,
define the fail-safe behavior, configure limit values, define filters and linearizations
and adjust the calibration parameters. All this configurations may also affect the
cyclic communication. If for example the operating mode is changed additional
variables may be put on the PROFIBUS.