Primary and backup CI854A need different node addresses on PROFIBUS. While
the primary node address is configured via the settings in the HW Configuration
Editor the node address for the backup module is defined by the fixed offset -1 to the
node address of the primary module. Therefore you cannot configure the node
address 0 on PROFIBUS with CI854/CI854A. This is reserved for redundancy.
During normal operation only the primary CI854A has communication with the
slave units. The backup unit is in hotstandby mode. It is configured by the controller
and synchronized by the primary unit. If there is a failover because of for example a
disturbed PROFIBUS communication, primary and backup module change the node
addresses. During failover the former primary module will get reset.