开关输入A/B/C/D状态:为了帮助故障排除,可以使用这些消息验证每个开关的状态。一条单独的消息显示由相应名称标识的每个输入的状态,如第2章中的接线图所示。对于相应开关端子上的干触点闭合,消息将显示为CLOSED.TIME/DATE:当前时间和日期显示在此消息中。PQM使用内部生成的软件时钟,该时钟在控制电源断开后运行约一小时。要设置时钟,请参阅设定点页面S1 PQM SETUP\clock。如果断电超过约1小时且时钟值丢失,则会出现S4警报/控制\其他\时钟未设置警报。实际值]]A2状态]可编程]消息电话:905-294-6222 www.GEmultily.com]]实际值]]A3功率分析实际]A2页结束
SWITCH INPUT A/B/C/D STATE: To assist in troubleshooting, the state of each switch can be verified using these messages. A separate message displays the status of each input identified by the corresponding name as shown in the wiring diagrams in chapter 2. For a dry contact closure across the corresponding switch terminals the message will read CLOSED.TIME/DATE: The current time and date is displayed in this message. The PQM uses an internally generated software clock which runs for approximately one hour after the control power has been removed. To set the clock, see setpoints page S1 PQM SETUP \ CLOCK. The S4 ALARMS/ CONTROL \ MISCELLANEOUS \ CLOCK NOT SET ALARM alarm occurs if power has been removed for longer than approximately 1 hour and the clock value has been lost.ACTUAL VALUES ]] A2 STATUS ] PROGRAMMABLE ] MESSAGE PHONE: 905-294-6222 www.GEmultilin.com ]] ACTUAL VALUES ]] A3 POWER ANALYSIS ACTUAL ] END OF PAGE A2