显示的用户定义名称和单位将根据连接的模拟输入更改为相应的值。有关用户定义的名称和单位以及模拟输入多路复用的信息,请参阅第4章“模拟输入”。只有在编程时间超过报警阈值时,才会显示报警消息。当报警分配给输出继电器时,可以将继电器设置为解锁或锁定。当报警设置为未锁定时,当报警条件不再存在时,报警将自动重置。如果报警设置为锁定,则需要键盘重置或串行端口重置。如果检测到PQM硬件中的故障,则会发生SELF TEST ALARM(自检报警)。该报警永久分配给报警输出继电器,不可由用户配置。如果出现此警报,请联系GE Multilin服务部门。
The displayed user defined name and units will change to the corresponding values depending upon which analog input is connected. Refer to chapter 4, Analog Input, for information regarding user defined names and units as well as analog input multiplexing.The alarm messages appear only when the alarm threshold has been exceeded for the programmed time. When an alarm is assigned to an output relay, the relay can be set to be unlatched or latched. When the alarm is set as unlatched, it automatically resets when the alarm condition no longer exists. If the alarm is set as latched, a keypad reset or a serial port reset is required. The SELF TEST ALARM occurs if a fault in the PQM hardware is detected. This alarm is permanently assigned to the alarm output relay and is not user configurable. If this alarm is present, contact the GE Multilin Service Department.