GE DS215UCIAG1AZZ05A热燃机卡件
三相A/B/C功率因数:这些消息中显示三相真实功率因数以及各个相位A/B/C真实功率因数。相位A/B/C真实功率因数信息将仅针对WYE或3线直接连接系统显示。三相A/B/C最小功率:这些信息中显示了最小三相实际功率以及最小单相A/B/C实际功率。测量这些最小值的时间和日期也显示在这些消息中。该信息存储在非易失性存储器中,并在失去控制电源时保留。相位A/B/C最小实际功率信息将仅针对WYE连接系统显示。设置点S1 PQM SETUP\CLEAR DATA\CLEAR MIN/MAX POWER VALUES用于清除这些值。三相A/B/C kvar最小值:这些信息中显示了最小三相无功功率以及最小单相A/B/C无功功率。测量这些最小值的时间和日期也显示在这些消息中。
THREE PHASE/A/B/C POWER FACTOR: The three phase true power factor as well as the individual phase A/B/C true power factors is displayed in these messages. The phase A/B/C true power factor messages will be displayed only for a WYE or 3 WIRE DIRECT connected system. THREE PHASE/A/B/C kW MINIMUM: The minimum three phase real power as well as the minimum individual phase A/B/C real power is displayed in these messages. The time and date at which these minimum values were measured is also displayed in these messages. This information is stored in non-volatile memory and will be retained during a loss of control power. The phase A/B/C minimum real power messages will be displayed only for a WYE connected system. The setpoint S1 PQM SETUP \ CLEAR DATA \ CLEAR MIN/ MAX POWER VALUES is used to clear these values. THREE PHASE/A/B/C kvar MINIMUM: The minimum three phase reactive power as well as the minimum individual phase A/B/C reactive power is displayed in these messages. The time and date at which these minimum values were measured is also displayed in these messages.