• UNDERVOLTAGE LEVEL: When the voltage on one, two, or three phases drops to or below this level, an undervoltage condition occurs. The number of phases required is determined by the PHASES REQUIRED FOR U/V OPERATION setpoint. To clear the undervoltage condition, the level must increase to 103% of the UNDERVOLTAGE LEVEL setting. For example, if the UNDERVOLTAGE LEVEL is set to 4000 V, the condition clears when the voltage in the appropriate phase(s) increases above 4120 V (4000 × 1.03). This hysteresis is implemented to avoid nuisance alarms due to voltage fluctuations. • UNDERVOLTAGE DELAY: If the voltage drops to or below the UNDERVOLTAGE LEVEL setpoint value and remains this way for the time delay programmed in this setpoint, an undervoltage condition will occur.