Selecting auxiliary relay will cause the auxiliary relay to activate for a neutral overcurrent condition but no message will be displayed. This is intended for process control. • NEUTRAL OVERCURRENT LEVEL: When the neutral current equals or exceeds the level set by this setpoint, a neutral overcurrent condition will occur. • NEUTRAL OVERCURRENT DELAY: If the neutral current equals or exceeds the NEUTRAL OVERCURRENT LEVEL setpoint value and remains this way for the time delay programmed in this setpoint, a neutral overcurrent condition will occur. • UNDERVOLTAGE RELAY: Undervoltage can either be disabled, used as an alarm or as a process control. Set this setpoint to off if the feature is not required. Selecting alarm relay will cause the alarm relay to activate and display an alarm message whenever an undervoltage condition exists. Selecting auxiliary relay will cause the auxiliary relay to activate for an undervoltage condition but no message will be displayed. This is intended for process control.