有时可能需要使用PQM键盘停止数据记录器,然后使用计算机提取记录的信息。STOP DATA LOG(停止数据日志)1和2设置点允许用户停止各自的数据日志。这些设定值还显示相应数据记录器的当前状态。有关数据记录器实施的详细说明,请参阅附录。NON-FAILSAFE:继电器线圈在非激活状态下未通电。失去控制电源将导致继电器保持在非激活状态。也就是说,非故障安全报警继电器不会在失去控制电源时发出警报。接线图中的触点配置显示为继电器编程为非故障安全,且控制电源未接通。故障安全:继电器线圈在非激活状态下通电。失去控制电源将导致继电器进入激活状态。也就是说,故障保护报警继电器将在失去控制电源时发出警报。当施加控制电源时,触点配置与编程为故障保护的继电器的接线图所示相反。
On occasions it may be necessary to stop the data loggers using the PQM keypad and then a computer to extract the logged information. The STOP DATA LOG 1 and 2 setpoints allow the user to stop the respective data log. These setpoints also display the current status of the respective data logger. Refer to the Appendix for a detailed description of the data logger implementation.NON-FAILSAFE: The relay coil is not energized in its non-active state. Loss of control power will cause the relay to remain in the non-active state. That is, a non-failsafe alarm relay will not cause an alarm on loss of control power. Contact configuration in the Wiring Diagrams is shown with relays programmed non-failsafe and control power not applied. FAILSAFE: The relay coil is energized in its non-active state. Loss of control power will cause the relay to go into its active state. That is, a failsafe alarm relay will cause an alarm on loss of control power. Contact configuration is opposite to that shown in the Wiring Diagrams for relays programmed as failsafe when control power is applied.