PQM电压输入应使用额定值为2A的HRC熔断器直接连接,以确保足够的中断容量。该图显示了典型的三线三角形连接,可覆盖任何电压范围。选择S2 SYSTEM SETUP(S2系统设置)\ CURRENT/VOLTAGE CONFIGURATION(电流/电压配置)\VT WILING:3 WIRE DELTA(2个VT)设定点。电压小于等于600 V(L-L)的三线制系统可以直接连接到PQM,而无需VT。选择S2系统设置\电流/电压配置\ VT接线:3线直接设置点。PQM电压输入应使用额定为2安培的HRC保险丝直接连接,以确保足够的中断容量。对于单相连接,仅将电流和电压连接到a相输入。忽略所有其他输入。选择S2系统设置\电流/电压配置\ VT接线:单相设置点。
The PQM voltage inputs should be directly connected using HRC fuses rated at 2 A to ensure adequate interrupting capacity.This diagram shows the typical 3-wire delta connection which will cover any voltage range. Select the S2 SYSTEM SETUP \ CURRENT/VOLTAGE CONFIGURATION \ VT WIRING: 3 WIRE DELTA (2 VTs) setpoint.Three-wire systems with voltages 600 V (L-L) or less can be directly connected to the PQM without VTs. Select the S2 SYSTEM SETUP \ CURRENT/VOLTAGE CONFIGURATION \ VT WIRING: 3 WIRE DIRECT setpoint. The PQM voltage inputs should be directly connected using HRC fuses rated at 2 amps to ensure adequate interrupting capacity For a single-phase connection, connect current and voltage to the phase A inputs only. All other inputs are ignored. Select the S2 SYSTEM SETUP \ CURRENT/VOLTAGE CONFIGURATION \ VT WIRING: SINGLE PHASE setpoint.