DS200TCDAH1BGD模块备件
详细规范
带HART参数规范的模拟输出输出类型4-20 mA电流回路输出通道32每个模块1最大值(带或不带开路检测)输出纹波<125 mV,在电源线频率下,峰值电压250 负载输出温度漂移0.001%满量程/°C输出回读精度0.25%满量程输出电流线性度±0.05%满量程标称分辨率12位校准精度0.1 W闭合触点5 kΩ>0.25 W闭合触点检测1.8mA<I<6 mA 1开路触点检测0.7 mA<I<1.8 mA 2开路线检测I<0.7 mA输入滤波器一阶低通16 Hz注1:在24 VDC,等于8.57 KΩ>R>4 KΩ(其中R=总回路电阻)注2:24 VDC时,等于26.7 KΩ>R>10 KΩ详细规范–无OWD参数规范的数字输入开路电压24 VDC闭合触点电流7 mA±5%,开路状态检测3.5 mA±5%后,闭合状态检测后闭合触点检测I>2.81mA 1断开触点检测I<1.8mA 2)
输入滤波器一阶低通16 Hz注
1:在24 VDC时,等于R<8.57 KΩ(其中R=总回路电阻)注2:在24 V直流时,等于26.7 KΩ>R>10 KΩExperion Series-C I/O规范,EP03-490-520 43版本1.5霍尼韦尔专有2021 12月详细规范-数字输出参数规范每个模块最大32个输出通道(带或不带开路检测)4个输出型固态电源,防短路3个负载电流0mA 1mA最小到0.5A最大每个通道2个最大9 A每个模块1个最大通态电压24 V(典型),负载电流@0.5A关闭状态电压0v VDC(最大值)关闭状态泄漏电流<0.1 mA无切换(0ms)时输出到现场的间隙(0电流)(仅适用于冗余)
Detailed specifications
Analog output type with HART parameter specification 4-20 mA current loop output channel 32 maximum value of each module 1 (with or without open circuit detection) output ripple<125 mV, Peak voltage 250 Ω Load output temperature drift 0.001% Full scale/° C Output back reading accuracy 0.25% Full scale output current linearity ± 0.05% Full scale nominal resolution 12 bit calibration accuracy 0.1 W Closed contact 5 k Ω>0.25 W Closed contact detection 1.8 mA<I<6 mA 1 Open contact detection 0.7 mA<I<1.8 mA 2 Open line detection I<0.7 mA Input filter First order low-pass 16 Hz Note 1: At 24 VDC, Equal to 8.57 K Ω>R>4 K Ω (where R=total loop resistance) Note 2: When 24 VDC, it is equal to 26.7 K Ω>R>10 K Ω Detailed specification – open circuit voltage of digital input without OWD parameter specification 24 VDC closed contact current 7 mA ± 5%, after open circuit status detection 3.5 mA ± 5%, closed contact detection I>2.81mA 1 open contact detection I<1.8mA 2)
Input filter 1st order low-pass 16 Hz Note
1: At 24 VDC, it is equal to R<8.57 K Ω (where R=total loop resistance) Note 2: At 24 V DC, it is equal to 26.7 K Ω>R>10 K Ω Experience Series-C I/O specification, EP03-490-520 43 version 1.5 Honeywell proprietary December 2021 detailed specification - digital output parameter specification Each module has a maximum of 32 output channels (with or without open circuit detection) 4 output solid-state power supplies, Short circuit proof 3 load currents 0mA, 1mA, minimum to 0.5A, maximum 2 per channel, maximum 9 A, each module, maximum on state voltage, 24V (typical), load current @ 0.5A, off state voltage, 0v VDC (maximum), off state leakage current<0.1 mA, no switching (0ms), clearance output to the site (0 current) (only applicable to redundancy)