ACS-AP-W工控DCS系统备件
电压监控输入
-紧凑型产品套件硬件选择器数据表此模块有16个数字输入。输入电压范围为18至30伏直流电,24伏时输入电流为6 mA。输入分为两个单独隔离的组,每组有八个通道和一个电压监控输入。每个输入通道由限流组件、EMC保护组件、输入状态指示LED和光学隔离栅组成。如果电压消失,过程电压监控输入将给出通道错误信号。错误信号可以通过ModuleBus读取。特点和优点24 V直流输入的16个通道,带电流消耗两组8个隔离组,带电压监控输入状态指示器一般信息文章编号3BSE008508R1型数字输入信号规格24V直流。通道数16信号类型电流吸收HART无SOE无冗余无高完整性无本质安全无机械S800 1数据表 | 2022-11-09 |版权所有©2022 ABB详细数据输入电压范围,“0”-30..+5 V输入电压范围、“1”15..30 V输入阻抗3.5 kΩ隔离与地分组隔离,2组8通道滤波时间(数字,可选)2、4、,8,16 ms电流限制传感器功率可由MTU最大现场电缆长度600米(656码)进行电流限制额定绝缘电压50 V电介质测试电压500 V交流功耗典型值1.8 W电流消耗+5 V模块总线50mA电流消耗+24 V模块总线0电流消耗+24V外部0诊断前LED的F(故障)、R(运行)、W(警告),通道1-16(“0”或“1”)监控过程电压,每组1个监控模块错误、
模块警告
通道错误的状态指示环境和认证CE标志是电气安全IEC 61131-2、UL 61010-1、UL 6110-2-201危险位置C1 Div 2 cULus、C1 Zone 2 cULus、ATEX Zone 2 Marine认证ABS、BV、DNV-GL、,LR防护等级IP20,符合IEC 60529腐蚀性环境ISA-S71.04 G3气候操作条件0至+55°C(储存-40至+70°C),RH=5至95%无冷凝,IEC/EN 61131-2污染程度2级,IEC 60664-1机械操作条件IEC/EN 61031-2 EMC EN 61000-6-4和EN 61000-6-2过电压类别IEC/EN 60664-1,EN 50178符合IEC 61140的I级设备;(接地保护)最大环境温度55°C(131°F),用于紧凑型MTU 40°C(104°F)的垂直安装,符合RoHS指令/65/EU(EN 50581:2012)符合WEEE指令/2012/19/EU兼容性与MTU TU810、TU812、TU814、TU818、TU830、TU833、TU838、TU850键控代码AA尺寸宽45 mm(1.77“)深102 mm(4.01”),111 mm(4.37“),包括连接器高度119 mm(4.7”)重量0.15 kg(0.33 lbs.)-相关产品2数据表 | 2022-11-09 |版权所有©2022 ABBTU810V1 TU812V1 TU824V1 TU830V1 TU843 TU838 TU850 3数据表DI820 | 2022-01-09 |版权©2021 ABB-解决方案。abb/compactproductsuite解决方案。abb/controlsystems 800xA和Symphony Plus是abb的注册商标。其他商标的所有权利归其各自所有者所有。我们保留对产品进行技术更改或修改本文件内容的权利,恕不另行通知。关于采购订单,应以商定的细节为准。ABB不对本文件中的任何错误或不完整信息承担任何责任。我们保留对此文档及其包含的项目和图像的所有权利。未经ABB事先书面许可,禁止复制、向第三方披露或使用本文件的内容(包括部分内容)。版权所有©2022 ABB保留所有权利4数据表| 2022-11-09 |版权所有©2 ABB
Voltage monitoring input
-Compact Product Kit Hardware Selector Data Sheet This module has 16 digital inputs. The input voltage range is 18 to 30 VDC and the input current is 6 mA at 24 volts. The inputs are divided into two separate isolated groups, each with eight channels and a voltage monitoring input. Each input channel is composed of current limiting component, EMC protection component, input status indication LED and optical barrier. If the voltage disappears, the process voltage monitoring input will give a channel error signal. Error signals can be read through ModuleBus. Features and Advantages 16 channels of 24 V DC input, two groups of 8 isolation groups with current consumption, general information of input state indicator with voltage monitoring Article No. 3BSE008508R1 digital input signal specification 24 V DC. Number of channels 16 Signal type Current absorption HART No SOE No redundancy No high integrity No intrinsic safety No machinery S800 1 Data sheet | 2022-11-09 | All rights reserved © 2022 ABB detailed data input voltage range, "0" - 30..+5 V input voltage range, "1" 15.30 V input impedance 3.5 k Ω isolation and ground group isolation, two groups of 8-channel filtering time (digital, optional) 2, 4, 8,16 ms Current limit sensor power can be limited by MTU's maximum field cable length of 600 meters (656 yards) Current limit Rated insulation voltage 50 V Dielectric test voltage 500 V AC power consumption Typical value 1.8 W Current consumption+5 V module bus 50 mA Current consumption+24 V module bus 0 Current consumption+24 V external 0 F (fault), R (operation), W (warning) of LED before diagnosis, channel 1-16 ("0" or "1") monitoring process voltage, 1 monitoring module error in each group
Module Warning
The status indication environment and certification CE mark of channel error are electrical safety IEC 61131-2, UL 61010-1, UL 6110-2-201 dangerous location C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 Marine certification ABS, BV, DNV-GL, LR protection grade IP20, in line with IEC 60529 corrosive environment ISA-S71.04 G3 climate operating conditions 0 to+55 ° C (storage - 40 to+70 ° C), RH=5 to 95% non condensing, IEC/EN 61131-2 pollution level 2, IEC 60664-1 Mechanical operating conditions IEC/EN 61031-2 EMC EN 61000-6-4 and EN 61000-6-2 Overvoltage category IEC/EN 60664-1, EN 50178 Class I equipment conforming to IEC 61140; (Grounding protection) The maximum ambient temperature is 55 ° C (131 ° F), which is used for the vertical installation of the compact MTU at 40 ° C (104 ° F), complies with RoHS directive/65/EU (EN 50,581:2012), complies with WEEE directive/2012/19/EU compatibility, and is compatible with MTU TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU850 keying code AA. The size is 45 mm wide (1.77 ") and 102 mm deep (4.01"), 111 mm (4.37 "), including 119 mm (4.7") connector height, 0.15 kg (0.33 lbs.) weight - related product 2 data sheet | 2022-11-09 | All rights reserved © 2022 ABBTU810V1 TU812V1 TU824V1 TU830V1 TU843 TU838 TU850 3 Data Sheet DI820 | 2022-01-09 | Copyright © 2021 ABB Solution. Abb/compactproductsuite solution. Abb/controlsystems 800xA and Symphony Plus are registered trademarks of abb. All rights to other trademarks belong to their respective owners. We reserve the right to make technical changes to the product or modify the content of this document without notice. For purchase orders, the agreed details shall prevail. ABB assumes no responsibility for any errors or incomplete information in this document. We reserve all rights to this document and the items and images it contains. Without the prior written permission of ABB, it is prohibited to copy, disclose or use the contents of this document (including some contents) to third parties. copyright © 2022 ABB All rights reserved 4 Data sheet | 2022-11-09 | All rights reserved © 2 ABB