控制软件10励磁系统UNITROL
1000软件功能概述软件功能UNITROL1005UNITROL1010 UNITROL2020 ECO•AVR/FCR/PF/VAR•限制器•保护/监控•软启动•电压匹配灯•历史记录器•Modbus TCP与操作员选择•旋转二极管监控BASIC•通过RS485(VDC)实现无功负载共享•双通道•自动同步(SYNC),60/50/16.7 Hz•电机启动支持(仅适用于UNITROL 1020)FULL•事件记录器•数据记录器•实时时钟•SNTP选项的时间同步•电力系统稳定器(PSS)BASIC BASIC FULL+PSS LIGHT LIGHT ECO ECO:ECO版本涵盖了成本敏感应用的基本功能。灯光:灯光版本增加了ECO标准功能,如旋转二极管监控和通过modbus远程控制。此外,一个被称为历史记录器的简化数据记录器允许用户跟踪最后两个小时的操作以进行分析。
串行通信
BASIC:BASIC版本是在同一母线上运行多台机器的理想解决方案。通过串行通信(VDC)实现准确的无功负载分担和快速自动同步是关键功能。此外,支持双通道功能和电机启动顺序功能。完整:复杂而苛刻的项目通常需要瞬态记录器和工厂时钟同步数据记录器功能。完整版能够满足这些要求。电力系统稳定器(PSS)PSS可以是提供标准IEEE 421.5-2005 2A/2B/2C功能的选项。PSS规定如今已包含在大多数电网规范中。PSS用于有效阻尼物理电网引起的功率振荡。即使在设备运行时,也可以通过CMT1000通过密码订购和轻松启用软件升级。完整UNITROL 1000产品组合的通用软件和工具:所有UNITROL 1000产品都基于相同的目标软件源代码,因此UNITROL1010/20和UNITROL2005具有相同的性能。相同的仿真模型可用于整个UNITROL1000产品系列,使UNITROL 1000产品适用于非常苛刻的网格代码应用
Control software 10 Excitation system UNITROL
1000 Software function overview Software function UNITROL1005UNITROL1010 UNITROL2020 ECO • AVR/FCR/PF/VAR • Limiter • Protection/monitoring • Soft start • Voltage matching lamp • Historical recorder • Modbus TCP and operator selection • Rotating diode monitoring BASIC • Reactive load sharing via RS485 (VDC) • Dual channel • Automatic synchronization (SYNC), 60/50/16.7 Hz • Motor starting support (UNITROL 1020 only) FULL • Event recorder • Data recorder • Real time clock • Time synchronization of SNTP option • Power system stabilizer (PSS) BASIC BASIC FULL+PSS LIGHT LIGHT ECO ECO: The ECO version covers the basic functions for cost sensitive sensing. Lighting: ECO standard functions are added to the lighting version, such as rotating diode monitoring and remote control via modbus. In addition, a simplified data logger called a history recorder allows users to track the last two hours of operations for analysis.
serial communication
BASIC: The BASIC version is an ideal solution for running multiple machines on the same bus. The key function is to realize accurate reactive load sharing and fast automatic synchronization through serial communication (VDC). In addition, it supports dual channel function and motor starting sequence function. Complete: Complex and demanding projects usually require transient recorder and factory clock synchronous data recorder functions. The complete version can meet these requirements. Power System Stabilizer (PSS) PSS can be an option to provide standard IEEE 421.5-2005 2A/2B/2C functions. PSS regulations are now included in most grid codes. PSS is used to effectively damp power oscillation caused by physical power grid. Even when the device is running, software upgrades can be ordered and easily enabled with a password through CMT1000. Common software and tools for the complete UNITROL 1000 product portfolio: All UNITROL 1000 products are based on the same target software source code, so UNITROL 1010/20 and UNITROL 2005 have the same performance. The same simulation model can be used for the entire UNITROL 1000 product family, making the UNITROL 1000 product suitable for very demanding grid code applications