5720001-EV DSCS140 工控备件
配置在LogicMaster 90中进行配置
或使用手持编程器作为进行配置。输入滤波器选择使用 CPU和某些其他CPU选项,该模块可配置为具有1mS或10mS输入滤波器。配置是针对模块的,而不是基于每个点;所有点具有相同的过滤时间。有关详细信息,请参阅适用的可编程控制器参考手册。中断当与 CPU一起使用时,输入点A1可配置为引起CPU中断。配置允许CPU在信号转换的上升沿或下降沿中断。中断响应不受输入滤波器时间选择的影响。有关详细信息,请参阅适用的可编程控制器参考手册。
Configuration is configured in LogicMaster 90
Or use the handheld programmer as the configuration. The input filter option uses the CPU and some other CPU options, and the module can be configured with a 1mS or 10mS input filter. The configuration is for modules, not for each point; All points have the same filter time. For details, refer to the applicable PLC reference manual. Interrupt When used with the CPU, input point A1 can be configured to cause a CPU interrupt. The configuration allows the CPU to interrupt on the rising or falling edge of the signal conversion. Interrupt response is not affected by input filter time selection. For details, refer to the applicable PLC reference manual.
模块机械
键控该模块包括一个机械键,可防止在给定插槽中一种模块类型意外替换另一种模块。该键适合连接器下方电路板上形状独特的区域。每个模块都有一个附带的钥匙。首次安装模块时,钥匙会锁在底板中央导轨上。拔出模块后,钥匙仍留在中央导轨中,将插槽配置为只接受相同的模块类型。如果在将钥匙锁在机架的中央导轨上后,需要更改模块在机架中的位置,则可以通过向上推动钥匙并将其从导轨上拔下,从而将其取下。然后,可以将其重新插入模块,并将模块插入机架中所需的位置。请注意,在IC697 PLC机架中,只能将电源置于最左边的机架位置,插槽1(与电源相邻)必须始终包含CPU(在机架0-CPU机架中)或总线接收器模块(在扩展机架中)
Modular machinery
Keying the module includes a mechanical key to prevent one module type from accidentally replacing another module in a given slot. This key is suitable for the uniquely shaped area on the circuit board below the connector. Each module has an attached key. When installing the module for the first time, the key will be locked on the central guide rail of the backplane. When the module is removed, the key remains in the central rail and the slot is configured to accept only the same module type. If you need to change the position of the module in the rack after locking the key on the central rail of the rack, you can remove the key by pushing it up and pulling it off the rail. You can then reinsert it into the module and insert the module into the desired location in the rack. Please note that in the IC697 PLC rack, the power supply can only be placed in the leftmost rack position, and slot 1 (adjacent to the power supply) must always contain the CPU (in rack 0-CPU rack) or bus receiver module (in expansion rack)