在禁止条件下,通道卡将继续读取
但是,气体传感器读数在发生以下情况时不采取任何措施:超过报警条件。
A1-红色LED
A1 LED指示预设的一级气体报警已启动超过。如果出现故障或抑制处于活跃状态。
d、 A2-红色LED
A2 LED指示预设的二级气体报警具有:已超过。在以下情况下,此警报将不起作用:故障或抑制条件激活。
A3-红色LED
A3 LED指示预设的第三级气体报警已启动超过。如果出现故障或抑制处于活跃状态。复位/选择按钮
前面板复位/选择按钮提供四种功能:根据其操作方式:
a、 报警复位
复位/选择按钮在瞬间按下时复位
任何锁定报警、非激活报警、故障、警告或信息消息,清除显示峰值读数指示器,并将
如果存在此类情况,则确认更新。
注:“非活动报警”描述了报警条件出现的情况
已清除,但由于已锁定,报警仍指示信息对于非锁定设置,指示的报警将清除报警条件清除时自动。
b、 频道选择
按下复位/选择按钮约1.5秒,选择控制卡,用于从工程卡。
c、 延长复位连续按下复位/选择按钮五秒钟:
i、 清除通道最大和最小气体读数。
二,。重置任何有效的短期(STEL)和长期(LTEL)
曝光警报将定时器清零。
iii.对于激活的延时功能,激活任何具有即将触发并清除任何保持的继电器。
频道取消选择
复位/选择按钮,当在如果选择了控制卡,则从工程卡功能。
注意:也可以通过按键取消选择控制卡
During the inhibit condition, the channel card will continue to read the
gas sensor reading, however, no action is taken in the event of an
alarm condition being exceeded.
c. A1 - Red LED
The A1 LED indicates that the preset first level gas alarm has been
exceeded. This alarm will not function in the event of either a fault or
inhibit condition being active.
d. A2 - Red LED
The A2 LED indicates that the preset second level gas alarm has
been exceeded. This alarm will not function in the event of either a
fault or inhibit condition being active.
e. A3 - Red LED
The A3 LED indicates that the preset third level gas alarm has been
exceeded. This alarm will not function in the event of either a fault or
inhibit condition being active.Reset/Select Push-button
The front panel RESET/SELECT push-button provides four functions
depending upon how it is operated:
a. Alarm Reset
The RESET/SELECT push-button, when pressed momentarily, resets
any latched alarm, non active alarms, faults, warning or information
messages, clears the display peak reading indicator and will
acknowledge an update if such a condition is present.
Note: 'Non active alarms' describe the occasion where the alarm condition
has cleared but the alarm is still indicated due to latched
information. For non-latched setups the indicated alarms will clear
automatically when the alarm condition clears.
b. Channel Select
The RESET/SELECT push-button, when pressed for approximately
1.5 seconds, selects the control card for operations controlled from
the Engineering Card.
c. Extended Reset
The RESET/SELECT push-button, when pressed continuously for
five seconds:
i. Clears the channel maximum and minimum gas readings.
ii. Resets any active short term (STEL) and long term (LTEL)
exposure alarms clearing the timer to zero.
iii. For active time delay functions, activates any relay with
impending trigger and clears any relay being held.
d. Channel Deselect
The RESET/SELECT push-button, when pressed momentarily while
a control card is selected, deselects the control card from the
Engineering Card functions.
Note: The control card may also be deselected by pressing the key