1.1.1扫描仪功能SST-PB3-CLX-RLL是用于1756(ControlLogix)背板和霍尼韦尔PlantScape系统。它支持CLX处理器和PROFIBUS网络上的DP远程输入/输出设备,用作PROFIBUS DP远程输入/输出扫描仪。
信息技术:
•DP主设备和从设备经过认证(带有Profibus固件版本7.25)
•最多支持15个仅侦听连接和1个输出连接
•作为主机,支持同步和冻结命令
•支持罗克韦尔的RSLogix 5000附加配置文件(AOP)
•最多可扫描125个从机

HESG324426R0001控制器•支持和扫描每个从机最多122个字的输入数据和122个字的输出数据
•可以驻留在本地或远程CLX机箱中的任何插槽中。最多可以有8个扫描仪在机架中。
•支持所有标准PROFIBUS波特率(9600、19200、31.25k、45.45k、93.75k、,187.5k、500k、1.5M、3M、6M、12M)
•支持以下DPV1主服务:
•1级:MSAC1\u读,MSAC2\u写
•2级:MSAC2\u启动、MSAC2\u读取、MSAC2\u写入、MSAC2\u空闲、,MSAC2\u中止
•最多可同时处理16个1级和16个2级命令
•使用DPV1时,最多可以处理16个2级连接(到16个2级DPV1从机)仅限2类通信
•可作为DPV0从机
•允许同时操作PROFIBUS主设备和从设备(高达12M)
•作为主机,最多支持1984字节的输入数据和1968字节的输出4个输入/输出页面中的数据
•作为主机,支持多达256个输入/输出模块的配置
1.1.1 Scanner Capabilities
The SST-PB3-CLX-RLL is the PROFIBUS scanner for the 1756 (ControlLogix) backplane and
Honeywell PlantScape system. It enables communication between a CLX processor and
DP remote I/O devices on a PROFIBUS network, acting as a PROFIBUS DP remote I/O
scanner. It:
•
DP Master and Slave Certified (with Profibus Firmware Revision 7.25)
•
Supports up to 15 listen-only connections plus 1 output connection
•
As a Master supports Sync and Freeze commands
•
Supports Rockwell’s RSLogix 5000 Add-on-Profile (AOP)
•
Can scan up to 125 slaves
•
Supports and scans up to 122 words of input data and 122 words of output data per slave
•
Can reside in any slot in the local or remote CLX chassis. You can have up to 8 scanners
in a rack.
•
Supports all standard PROFIBUS baud rates (9600, 19200, 31.25k, 45.45k, 93.75k,
187.5k, 500k, 1.5M, 3M, 6M, 12M)
•
Supports the following DPV1 Master services:
•
Class 1: MSAC1_Read, MSAC2_Write
•
Class 2: MSAC2_Initiate, MSAC2_Read, MSAC2_Write, MSAC2_Idle,
MSAC2_Abort
•
Can handle up to 16 Class 1 and 16 Class 2 commands simultaneously
•
Can handle up to 16 Class 2 connections (to 16 Class 2 DPV1 Slaves) when using DPV1
Class 2 Communication only
•
Can act as a DPV0 slave
•
Allows for simultaneous operation of PROFIBUS Master and Slave (up to 12M)
•
As a Master, supports a maximum of 1984 bytes of input data and 1968 bytes of output
data with in 4 I/O pages
•
As a Master, supports configurations with up to 256 I/O modules